7
EN
“UEX-PLUS” +030220621 - rel. 1.1 - 30.05.2008
installeruserservice
1. INTRODUCTION AND ASSEMBLY
1.1 humiSteam x-plus (UEX*)
Range of isothermal immersed electrode humidi ers with liquid crystal
display for the control and distribution of steam.
Models available (identi able from the code shown on the product):
UE001, UE003, UE005, UE008, UE009, UE010, UE015, UE018: steam
•
production capacity up to 18 kg/h (39.7 lb/h), water connections
under the base of the humidi er;
UE025, UE035, UE045, UE065: steam production capacity from 25 •
to 65 kg/h (55.1 to 144.3 lb/h), water connections on the side of the
humidi er;
UE090, UE130: steam production capacity from 90 to 130 kg/h (198.4 •
to 286.6 lb/h), water connections on the side of the humidi er.
1.2 Dimensions and weights
Models UE001 to UE018
Fig. 1.a
UE001 to UE008 UE009 to UE018
dimensions
mm (in)
A 365 (14.4) 365 (14.4)
B 275 (10.8) 275 (10.8)
C 620 (24.4) 712 (28.0)
weights kg
(lb)
packaged 16 (35.3) 20 (44.0)
empty 13.5 (29.8) 17 (37.5)
installed* 19 (41.9) 27 (59.5)
Models UE025 to UE065
Fig. 1.b
UE001 to
UE008
UE009 to
UE018
UE025 to
UE045
UE045** to
UE065
dimensions
mm (in)
A 365 (14.4) 365 (14.4) 545 (21.5) 635 (25.0)
B 275 (10.8) 275 (10.8) 375 (14.8) 465 (18.3)
C 620 (24.4) 712 (28.0) 815 (32.0) 890 (35.0)
weights
kg (lb)
packaged 16 (35.3) 20 (44.0) 39 (86.0) 51 (112.4)
empty 13.5 (29.8) 17 (37.5) 34 (74.9) 44 (97.0)
installed* 19 (41.9) 27 (59.5) 60.5 (133.4) 94 (207.2)
Models UE090 to UE0130
Fig. 1.c
UE090 UE130
dimensions
mm (in)
A 1150 (45.3) 1150 (45.3)
B 465 (18.3) 465 (18.3)
C 890 (35.0) 890 (35.0)
weights kg
(lb)
packaged 77 (169.8) 81 (178.6)
empty 70 (154.3) 74 (163.1)
installed* 130 (286.6) 170 (374.8)
*: in operating conditions
**: 230 Vac model
1.3 Opening the packaging
make sure the humidi er is intact upon delivery and immediately
notify the transporter, in writing, of any damage that may be due to
careless or improper transport;
move the humidi er to the site of installation before removing from
the packaging, grasping the neck only from underneath the base;
open the cardboard box, remove the protective material and remove
the humidi er, keeping it vertical at all times.
1.4 Positioning
the unit is designed to be mounted on a wall that is strong enough to •
support the weight in normal operating conditions (see Wall-mounting
below). Models UE025 to UE0130 can stand on the oor;
to ensure correct steam distribution, position the humidi er near the •
point of steam distribution;
make sure the humidi er is level, allowing the minimum clearances •
(see Fig. 1.d) for maintenance operations.
Important: during operation the metal casing heats up and the
rear part resting against the wall may reach temperatures in
excess of 60 °C (140 °F) .
Distances from walls
Models UE001 to UE018 Models UE025 to UE130
≥ 200
(7.9”)
<0,5°
≥ 200
(7.9”)
≥ 200
(7.9”)
≥ 400
(15.7”)
≥ 700
≥ 200
(7.9”)
≥ 200
(7.9”)
≥ 700
(27.6”)
≥ 200
(7.9”)
Fig. 1.d
1.5 Wall-mounting
Fit the humidi er on the wall using the support bracket and the screw kit
supplied (for the dimensions in mm see Fig. 1.d).
Assembly instructions:
unscrew the wall bracket from the humidi er bracket;
1.
fasten the wall bracket (see Fig. 1.e), checking horizontal position 2.
with a spirit level; if installed on a masonry wall, the plastic anchor
plugs (dia. 8 mm/0.31” ) and screws (dia. 5 mm x L= 50 mm/ 0.19” x L=
1.97” ) supplied can be used;
hang the appliance to the bracket using the slot on the top edge of
3.
the rear of the appliance;
B
A
C
B
A
C
B
A
C
Comments to this Manuals