Carel UE055 User Manual Page 46

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 45
46
EN
“UEX-PLUS” +030220621 - rel. 1.1 - 30.05.2008
installeruserservice
13.2 Technical speci cations
technical speci cations UEX models
UE001* UE003* UE003** UE005* UE005** UE008** UE009* UE010** UE015** UE018** UE025** UE035** UE045** UE065** UE090** UE130**
steam
connection 230 V 22/30 (0.9/1.2) 30 (1.2) 1x40 (1x1.6) 2x40
(2x1.6)
-- -- --
dia. mm (in) 400 V 22/30 (0.9/1.2) 30 (1.2) 1x40 (1x1.6) 2x40
(2x1.6)
2x40
(2x1.6)
4x40
(2x1.6)
outlet pressure limits Pa
(PSI)
0/1500 (0/0.218) 0/1300 (0/0.188) 0/1350 (0/0.196) 0/2000 (0/0.290)
supply water
connection 3/4” G
temperature limits °C (°F) 1 to 40 (33.8 to .104)
pressure limits (MPa) 0.1 to 0.8 (1 to 8 bar)
hardness limits (°fH) ≤ 40
instant  ow-rate (l/min) 0.6 1.1 5.85 (7 for UE045 A
230Vac)
714
conductivity range (μS/cm) 75 to 1250
drain water
connection dia. mm (in) 40 (1.6)
typical temperature °C (°F) ≤100 (212)
instant  ow-rate (l/min) 7 22.5 45
environmental conditions
ambient operating temp.
°C (°F)
1 to .40 (33.8 to .104)
ambient operating humidity
(% rH)
10 to 60
storage temperature °C (°F) -10 to 70 (14 to .158)
storage humidity (% rH) 5 to 95
index of protection IP20
electronic controller
controller HC**********
auxiliary voltage/frequency
(V - Hz)
24 / 50/60
maximum auxiliary power
(VA)
60 90
probe inputs (general
features)
can be selected for the following signals: 0 to 1 Vdc, 0 to 10 Vdc, 2 to 10 Vdc, 0 to 20 mA, 4 to 20 mA, NTC, 135-1000 ohm, 0-135 ohm.
input impedence: 60 kΩ with: 0 to 1 Vdc, 0 to 10 Vdc, 2 to 10 Vdc signals
50 Ω with: 0 to 20 mA, 4 to 20 mA signals
active probe power supply
(general features)
15 Vdc. 100 mA protected against short-circuits
+1 Vdc with 135 Ω load
alarm relay outputs(general
features)
250 V 5 A (2 A) - type of action-microswitching 1C
remote enable input
(general features)
voltage-free contact; max. resistance 50 Ω; Vmax= 24 Vdc; Imax= 6 mA
output
instant steam production
(1)
kg/h (lb/h)
1.5
(3.3)
3.0
(6.6)
3.0
(6.6)
5.0
(11)
5.0
(11)
8.0
(17.6)
9.0
(19.8)
10.0
(22)
15.0
(33)
18.0
(39.7)
25
(55.1)
35
(77.2)
45
(99.2)
65
(143.3)
90
(198.4)
130
(286.6)
power input at rated
voltage (kW)
1.12 2.25 2.5 3.75 3.75 6.0 6.75 7.5 11.25 13.5 18.75 26.25 33.75 48.75 67.5 97.5
Tab. 13.b
* single-phase, ** three-phase.
(1)
= the average steam production is a ected by factors such as: ambient temperature, water quality, steam distribution system
13.3 Models of steam hoses
UEX models
code
UE001X
UE003X
UE005X
UE008X
UE009X
UE010X
UE015X
UE018X
UE025X
UE035X
UE045X
UE065X
UE090X
UE130X
steam outlet dia.
mm (in)
22
(0.9”)
22
(0.9”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
40
(1.6”)
40
(1.6”)
40
(1.6”)
2x40
(2x1.6”)
2x40
(2x1.6”)
4x40
(2x1.6”)
max. capacity
kg/h (lb/h)
1/1.5
(2.2/3.3)
3
(6.6)
5
(11)
8
(17.6)
9
(19.8)
10
(22)
15
(33)
18
(39.7)
25
(55.1)
35
(77.2)
45
(99.2)
65
(143.3)
90
(198.4)
130
(286.6)
CAREL steam hoses
code ID mm (in)
1312360AXX 22 (0.9”) --------- - - -
1312365AXX 30 (1.2”) - - √√√√√√- - - - - -
1312367AXX 40 (1.6”) - - ------
Tab. 13.c
Page view 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 ... 59 60

Comments to this Manuals

No comments