“UEX-PLUS” +030220621 - rel. 1.1 - 30.05.2008
installeruserservice
For the connecting remove the cover , and connect cards optional
connector J19.
M.2 M.7
J19
M.8
Modbus® protocol
The protocol Modbus ® is available by selecting from the menu installer
mask supervisor.
Chapter 13.6 shows a list of variables and the corresponding addresses.
For multiple read/writes, the maximum number of “Register or “Coil”
variables is 20.
The following functions are available:
MB_READ_COIL_STATUS 1: used to request the status (ON or OFF)
of a certain number of “Coil” variables (binary, 1 bit), starting from the
speci ed address.
MB_READ_INPUT_STATUS 2: operationally identical to the above.
MB_READ_HOLDING_REG 3: used to request the value of a
consecutive block of “Register variables (nu-meric, 16 bit).
MB_READ_INPUT_REG 4: operationally identical to the above.
MB_FORCE_SINGLE_COIL 5: used to set the status of an individual
“Coil” variable (binary, 1 bit) to ON or OFF (specifying the address of the
bit in question).
MB_PRESET_SINGLE_REG 6: used to set the value of an individual
“Register” variable (numeric, 16 bit).
MB_FORCE_MULTIPLE_COIL15: used to set the status of a consecutive
block of “Coil” variables (binary, 1 bit) (specifying the number of bits and
number of bytes).
MB_PRESET_MULTIPLE_REG16: used to set the value of a consecutive
block of “Register variables (nume-ric, 16 bit).
Exceptions managed:
01 illegal function
02 illegal data address
Important: for the tLAN and pLAN connections in residential
household (IEC EN 55014-1) and residential (IEC EN 61000-6-3)
environments, use shielded cable (with shield connected to GND). This
warning also applies to the cables leaving the unit.