12
Alimentación trifásica (SD 360-384)
Three-phase power supply (SD 360-384)
TAM 1
TAM 2
Drain pump 2
20 21
External signal Alarm
Remote On/Off
= Primary voltage
B = 200 - 208V~
C = 220 - 240V~
D = 380 - 415V~
E = 440 - 480V~
F = 575V~
***
Line
F2 2A ATM/gG
F3 4A ATM/gG
F1 4A ATM/gG
230V
0V
***
24V
0V
F4 4A GT
Transformer 400 VA
ON/OFF
X1
X2
56 57 58 59 60 70 71 72
Optional fan
K2
Conduct imeter
L1 L2 L3 PE
Boiler 1
52 53 67 66
50 51
Control CDC / P / H / D / T
+12 S1 S2 GND -12 N0 C NC
65
64
55
54
G G0
68 69 61 62 56 57 58 59 60 70 71 72
12A
11A
10A
9A
8A 7A 6A 5A 4A 3A 4B 3B 2B 9C 8C 7C
1B 1C 2C 4C 3C
13A
5C 1A 6C 2A
Drain
Fill
GND
I sig
Board 98C153C005
65
64
10A
9A
Drain Fill
Boiler 2
K1 K2
Drain pump 1
Fill valve 2
Fill valve 1
Mounted on
transformer
K1 K2K1 K2K1
* Los bornes 66-67, solo están presentes con el control CDD, para gestionar la dehumidificación (ver pág. 20). El control
CDD, se puede combinar con el control “Macrobase”, para gestionar la humidificación/dehumidificación de una central de
tratamiento de aire. Características de la salida 66-67: I max 5 mA, V max 30 V~
The connections 66-67 are present only on the CDD controller for the dehumidifier management (see on page 20). The
CDD controller can be compled with the Macrobase controller for the humidification/dehumidification management of air
handling units. Output 66-67 characteristics: Imax 5mA; Vmax 30V~