CAREL heaterSteam
4
How The heaterSteam Works
Electric immersion resistance heaters are contained inside a stainless steel canister. When humidity is needed,
the elements heat the water into steam. The heaterSteam is unique in that the heating elements are encased
in Aluminum to permit them to operate dry without burning up. Special electronics even detect when
maintenance is needed.
UR002 to UR010 UR020 to UR060
1. Klixon temperature sensor
2. Solid State Relay(s)
3. Motor protector
4. Fuses
5. Power contactor
6. Power transformer
7. Relay board
8. On/Off – Manual drain
switch
9. Power terminals
10. Power cable strain relief
11. Cooling fan
12. Controller
13. Drain valve
14. Fill Valve
15. Cylinder
16. Level floats
17. Locking lever
19. Drain pump
Operation:
On a call for humidity, the HeaterSteam humidifier first checks the incoming water conductivity, water level and
then runs diagnostics. The heating elements are then energized, and if modulating, the SSRs are pulsed to
control the steam output to match demand. Periodically, the humidifier will drain away part of the cylinder water
and replace it with fresh water to dilute the minerals in the cylinder and extend the maintenance cycle. Full
diagnostics monitor the incoming water conductivity, foaming action in the steam cylinder, heater operation and
output, and water level.
Features:
Automatic level control and draining by conductivity
Overheat protection of heaters to prevent burn-out and predict maintenance
Backflow prevention
Anti-Foaming System
Page view 3