1.5 Connect Power Wiring
Before connecting any power supply, check the data label found inside the
electrical compartment door and insure that the unit is configured for the
electrical supply to be connected. If it does not match, do not connect power -
call your Carel representative. On the bottom of all units are wiring holes that
permit external wiring to enter the unit. Insert the power wires through these
holes and secure the strain reliefs.
Inside the electrical compartment of the humidifier are power terminals marked N and L for single phase, and
L1, L2 and L3 for three phase units. A ground terminal is also provided. Connect power wiring to these
terminals only. An external, fused disconnect should be provided according to local and national electrical
codes.
V UNIT MODEL NUMBER, CAPACITY, AMPERAGE, WATTAGE
Ph.
FACTOR
UR002 UR004 UR006 UR010 UR020 UR027 UR040 UR060
Lbs/hr 4.4 7.3 13.6
208 Kg/hr 2 3.3 6.22
1 Amps 7 11.8 22.2
Watts 1500 2500 4600
Lbs/hr 5.3 8.8 13.2
230 Kg/hr 2.4 4 6
1 Amps 7.8 13 19.6
Watts 1800 3000 4500
Lbs/hr 13.6 22 47.5 63.4
208 Kg/hr 6.2 10 21.6 28.8
3 Amps 12.8 20.8 45.1 60
Watts 4600 7500 16200 21600
Lbs/hr 13.2 22 43.3 58.1
230 Kg/hr 6 10 19.7 26.4
3 Amps 11.3 18.8 37.1 49.8
Watts 4500 7500 14700 19800
Lbs/hr 13.2 22 46.2 57.9 88.9 133.3
460 Kg/hr 6 10 21 26.3 40.4 60.6
3 Amps 5.7 9.4 19.7 24.7 38.1 57.1
Watts 4500 7500 15700 19700 30300 45500
Lbs/hr 13.2 22 43.1 57.2 88.2 132.2
575 Kg/hr 6 10 19.6 26 40.1 60.1
3 Amps 4.5 7.5 14.8 19.4 30.2 45.3
Watts
4500 7500 14600 19500 30000 45100
Allowed voltage tolerance: +-10% of rated voltage.
Internal fuses
Fuse Sizes for Models
UR002 UR004 UR006-1Ph. UR006-3Ph. UR010 UR020 UR027 UR040 UR060
Fuses 1, 2 transformer primary 1A, 10.3x38mm fast blow
0.5A, 10.3x38mm (460,575V) fast blow
1A, 10.3x38mm (208,230V) fast blow
Fuse 3 drain pump 1A, 10.3x38mm, fast blow
Fuse 4 transformer secondary 2.5A, 5x20 ceramic, slow blow
Fuses F5, F6, F7 (208,230V) 40A, J 35A, J
Fuses F8, F9, F10 (208,230V) 40A, J 50A, J