Carel heaterSteam Specifications Page 25

  • Download
  • Add to my manuals
  • Print
  • Page
    / 52
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 24
Installation, Operation & Maintenance Manual
25
Code Range Default Unit Description Notes
C1 0 to 4 4
enable keypad and
remote control
Keypad: Remote control:
0= K: read all parameters, modify C1
R: read/modify P, d and St
1= K: read and modify all parameters
R: read/modify P, d and St
2= K: read all parameters, modify C1
R: read P, d and St
3= K: read and modify all parameters
R: read P, d and St
4= K: read and modify all parameters
R: read/modify all
C2 0 to 99 0
code for enabling
remote control
C3 0 to 199 1 serial address
C4 0 to 3 3 baud rate
0= 1200
1= 2400
2= 4800
3= 9600
C5 0 to 11 0 bits, parity, stop bits
0= 8,N,2 6= 7,N,2
1= 8,N,1 7= 7,N,1
2= 8,E,2 8= 7,E,2
3= 8,E,1 9= 7,E,1
4= 8,O,2 10= 7,O,2
5= 8,O,1 11= 7,O,1
C6 0 to 199 0 ms serial reply send delay
C7 0 to 3 0
graphic germinal
configuration
0= standard terminal
1= terminal with On/Off command
2= terminal with On/Off and control sensor
3= terminal with On/Off and hi-limit sensor