Installation & Maintenance Manual__________
30
9. Control of the Humidifier
Controller with Alphanumeric Display:
# Description
1
button to access the working parameters (codes Px,dx); it also resets the internal alarm relay
2
allows you to display the unit of measure of the displayed value; press for 2 seconds to allow display/programming of set
point; when pressed and held down for 5 seconds with PRG it allows you to access the menu for programming the
configuration parameters
3
button to display the measured value of the main sensor (in ON/OFF control it is always 0); during programming, it increments
the displayed value
4
button to display the measured value of the secondary sensor (if used); in programming mode it decrements the displayed
value.
5
display provides 2 1/2 digit code for indication of digital values and the codes of any alarms present; during programming the
display shows parameter codes and their values
6
LED indicating the decimal point
7
LED indicates that the displayed value is actually 1/1000th the actual value; multiply by 1000 to get actual value
8
LED indicating dehumidify mode
9
LED indicating alarm relay status
10
LED indicating steam production in progress, if flashing, it indicates the quantity of steam produced is less than requested
11
LED indicating the status of the fill valve
12
LED indicating the status of the drain valve
9.1 Starting Sequence
When the humidifier is started it goes through a sequence of operation that is displayed on the front panel by
the LEDs in the following manner:
1 - INITIAL START 2 - INITIALIZATION 3 - FUNCTIONAL PHASE
In this phase, which lasts 1
second, all LEDs on the display
are lit.
During this phase, which lasts
for 4 seconds, the three LEDs
shown are illuminated.
The humidifier begins to function normally and the control
indicates the following:
Autotest status
steam production (in %) with external proportional control;
the display of the main sensor in stand-alone mode;
in case the humidifier is disabled, two dashes will appear
flashing in the two right digits
In case of an alarm, the alarm LED will turn on and the corresponding alarm code will be displayed.
2
6
911
4
1
10 812 7