Installation & Maintenance Manual__________
16
5. Connect Control Wiring
A typical humidifier control system includes a wall or return duct sensor or controller, a high limit duct humidistat
and an air-proving switch. Placement of these devices is critical to proper operation of the overall system.
5.1 Controls Placement
(See following diagram)
The return air RH sensor must always be located BEFORE any outside air intake, in order to insure accurate
sensing of the air from the space. Alternatively, a room RH sensor or humidistat can be used. Room sensors
should be located on an inside wall or post and should not be hit by any discharge air streams from ducts. In a
100% outside air system, the RH sensor may be placed in the supply duct, at least 10 feet down stream of the
distributor pipe to act as both hi-limit and control.
The airflow switch must be positioned to accurately open on a loss of airflow, to prevent the humidifier from
running when there is no air to absorb the moisture.
The hi-limit humidistat must be positioned far enough down stream of the steam distributor pipe(s) to prevent
it from getting wet, but still allow it to accurately prevent over humidification of the duct that could result in
condensation.