SE process chiller +030220416 - rel. 1.1 - 27.04.2010
Hc1 to Hc4: compressor operating hour limit exceeded warning
When the number of operating hours for the compressor exceeds the maintenance threshold (as default
equal to zero, and consequently the function is disabled), the maintenance request signal is activated.
The buzzer and the alarm relay are not activated, however the warning relay is activated (with the
expansion card fi tted).
Epr, EPb: EEPROM error
A problem has occurred when saving the parameters to the unit’s non-volatile memory (EEPROM); in the
event of an Epr error, the µC
2
SE continues to perform the control functions with the data present in the
volatile memory (RAM), where there is a physical copy of all of the data. After the fi rst power failure the
confi guration will be lost.
The buzzer and the alarm relay are not activated. If the occurs when starting the unit, “EPb”, the controller
will not operate.
ESP: communication error with expansion card
If the controller loses communication with the expansion card, the entire system will be stopped to avoid
adversely affecting the unit. The alarm relay is activated and the display will show the message, with the
red LED on steady.
EL1-2: warning, zero crossing error circuit 1-2
If the controller detects errors in the power supply, control may be lost over the fan speed. In this case,
the display will show a warning, and the fans will be controlled at maximum speed. The alarm is reset
automatically, so as to not affect the operation of the unit. If the expansion card is used, the warning relay
is activate)
dF1-2: warning, end defrost circuit 1-2 due to maximum time
If the defrost ends after the maximum time when end defrost by temperature or from external contact
has been selected, the unit displays the text dF1 for circuit 1 or dF2 for circuit 2. The message is cancelled
using the delete alarm procedure or when the next correct defrost cycle is completed. The buzzer and the
alarm relay are not activated. If the expansion card is used, the warning relay is activated (if used).
A1: antifreeze alarm outlet limit circuit 1
The alarm is only detected in water chillers (H01= 2, 3, 4, 5 or 6) by the evaporator water outlet
probe (B2/B6) or, if the electronic expansion driver (EVD) is connected to the tLAN, based on the
evaporation temperature sent by the driver. The evaporator water outlet temperature is compared
against the threshold A01, while the evaporation temperature is compared against the threshold A14. The
compressors in circuit 1 and the condenser fans in circuit 1 are immediately stopped, the buzzer and
alarm relay are activated, and the display starts fl ashing. If the µC
2
SE is in Standby, the alarm condition is
not detected, and only the heaters are managed. Reset depends on parameter P5:
1. in the event of automatic reset, the unit restarts automatically if the temperature is above the value
A01+A02 or A14+A02.
2. in the event of manual reset, the unit can restart manually even if the alarm is active.
After the time A03, if the alarm persists the unit will stop again.
For air/air units the parameter becomes the antifreeze-outlet limit alarm set point. If the outlet limit is
active, the freecooling damper is forced closed and the message SUL is shown on the display.
A2: antifreeze alarm circuit 2
As for A1 but relating to circuit 2
Ht: high temperature warning
This alarm is activated when the threshold is exceeded (read by B1), set for the parameter P16. It is
delayed at power ON by the parameter P17 and causes the activation of the alarm relay and the buzzer,
without deactivating the outputs. It is reset automatically when conditions that caused the alarm are no
longer present.
Lt: low temperature warning
For direct expansion units (H01=0, 1) the alarm is used to measure a low room temperature using probe
B1 or B2 (depending on par. A06).
The alarm may be reset manually or automatically, and depends on the parameter P05. If the expansion
is present, the corresponding relay is activated; in the event of µC
2
SE module only, the alarm relay will be
used.
AHt: high temperature warning when starting the system
The advice does not activate the relay, and displays the message “AHt”.
ALt: low temperature warning when starting the system
The advice does not activate the relay, and displays the message “ALt”.
ELS/EHS: warning, low/high power supply alarm
If the power supply voltage is too low or too high, the corresponding message is displayed. In these
cases, the correct operation of the µC
2
SE is no longer guaranteed. In the low voltage conditions only the
requests to deactivate the loads are effected. Any start-up requests remain pending. The high voltage
condition involves the deactivation of all the energised relays.
L: Low load warning
The warning does not activate the relay and displays the message “ L ”; reset is automatic.