62 MPXPRO” +030220186 - rel. 1.0 - 22.05.2007
CONVERTERTERMINAL
USBtLAN
PC
commissioning cable
Fig. 7.f
MASTER SLAVE
USB
RS485
tLAN
PC
Fig. 7.g
E N G L I S H
of the commissioning software will be available with software release.
• Commissioning via terminal/display (with IROPZTLN00 converter)
This is used to connect a supervisor PC, running the special software, to an MPXPRO controller via a
terminal or display fitted with the commissioning port.
To use this commissioning connection:
Identify the connection port located under the keypad on the IR* U* and IR* X* terminals/displays (see
the figure to the side)
Connect the USB ports on the converter and the PC using a USB cable
If the PC is connected to a master unit, the software can access the parameters and status variables
relating to the master controller, as well as the parameters (unit and operating) and status variables of
the slave controllers in the sub-network. If the connection is made to the terminal on a slave, only the
parameters (unit operating operation) and status variables of that slave can be accessed.
• Commissioning via the RS485 supervisor port (with CVSTDUMOR0 converter)
As well as the connection via the terminal, MPXPRO can also be connected to a PC via the RS485 super-
visory network. In this case, the PC will only be connected to the master unit. Access to the parameters
(unit and operating operation) and status variables relating to the slaves connected to the master will be
available via the master controller (see the figure to the side).
To use this commissioning connection:
Connect a master unit (board terminals 20, 21, 22) to the RS485 output on the CVSTDUMOR0 conver-
ter, using an RS485 cable.
Connect the USB ports on the converter and the PC using a USB cable
N.B.: To manage the slave units in the sub-network, make sure that these are correctly connected to the
master via the tLAN.
for the connections with the MPXPRO board, see p. 12for the connections with the MPXPRO board, see p. 12