56 MPXPRO” +030220186 - rel. 1.0 - 22.05.2007
E N G L I S H
dS1 Compressor off time in “Sequential stop” defrost mode
Code UOM Min Max Def.
dS1 min 0
45 0
This represents the initial counter starting time in relation to the control stop time and the effective stop
time when reaching the maximum time ‘dS2’ for the activation of control.
dS1 = 0 Sequential stops disabledi
dS2 Compressor operating time in “Sequential stop” defrost mode
Code UOM Min Max Def.
dS2 min 0
240 120
This represents the value initial counter starting time in relation to the control operating time, after which
a natural defrost is performed in sequential stops mode.
dS2 is only active if dS1 0.
• Power defrost
Power defrost is a special function on the MPXPRO that increases the end defrost threshold dt1 (dt2 for
the second evaporator) and/or the maximum defrost duration dP1 (dP2 for the second evaporator). The-
se increases allow longer and more effective defrosts. Power defrosts are performed upon each defrost
call in night status or when suitably configured by the RTC parameters (td1 to td8), to allow the user to
choose the most suitable conditions for this special procedure. Power Defrost is enabled when at least
one of the set increases, ddt or ddP, is other than zero.
ddt Additional end defrost temperature delta in “Power defrost” mode”
Code UOM Min Max Def.
ddt °C/°F -20.0
20.0 0.0
This sets the temperature value that is added to the end defrost threshold dt1 (dt2 for the auxiliary
evaporator).
Example. ddt = 0 °C: increased threshold not active in Power defrost
ddP Additional maximum defrost time delta in “Power defrost” mode”
Code UOM Min Max Def.
ddP min 0
60 0
This represents the time that is added to the maximum defrost duration dP1 (and dP2 for the auxiliary
evaporator).
Example. ddP= 0: increased duration not active in Power defrost
Example 2. If ddt>0 and ddP>0, then Power Defrost mode is enabled for both temperature and duration.
In this mode, any defrost calls when the controller is in night status or due to the RTC settings (td1 to td8)
with attribute P=1 modify the default settings.
The end defrost threshold temperature becomes
dt1P = dt1 + ddt
The maximum duration of defrost becomes
dP1P = dP1 + ddP
This effect is naturally extended to the second evaporator (dt2 and dP2).
6.6 Fan speed modulation
6.6.1. List of parameters
Code Parameter
Speed modulation
F5 Fan cut-off temperature (hysteresis 1°C)
F6 Maximum fan speed
F7 Minimum fan speed
F8 Fan peak speed time
F9 Select fan control with PWM output1/2 (with phase cutting speed control)
6.6.2 Speed modulation
MPXPRO can manage a maximum of 3 analogue outputs (this depends on the code of the board used):
− 1 0 to 10 Vdc output on the optional boards
− 2 PWM outputs (12V) on the main board
The modulation of the evaporator fan speed is one of the functions of these outputs and, in particular,
based on the standard factory configuration, modulation is managed using the 0 to 10 Vdc analogue
output on some optional boards. This unit configuration can only be changed using the commissioning
tool or programming key. In this mode, modulation can also be managed using the open collector/PWM
outputs. The modulation management algorithm is independent of the output used.
B@ dt1-dP1: End defrost temperature - Maximum
defrost duration, p.
29
A@ dt2-dP2: End defrost temperature - MaximumEnd defrost temperature - Maximum
defrost duration, second evaporator, p.
evaporator, p. 54
B@ td1…td8: Defrost events 1 to 8, p. 30
B@ dt1-dP1: End defrost temperature - Maximum
defrost duration, p. 29
A@ dt2-dP2: End defrost temperature - MaximumEnd defrost temperature - Maximum
defrost duration, second evaporator, p.evaporator, p. 54
B@ td1…td8: Defrost events 1 to 8, p. 30
MPXPRO board models, p. 10MPXPRO board models, p. 10