Installation, Operating & Maintenance Manual
33
Controller Action
H
Humivisor Causes Solution
H
Reset
display
Alarm
relay
Reset
relay
E0
E101
error
1. Reset the default parameters
(see Chap. 7.5)
2. If the problem persists, contact
the CARE service center
Shut-
down
By Carel
By
Carel
EI
E112
Error in the user
parameters
1. With the machine off check that
there are no defective electrical
connections or faults, then
reprogram the parameters
2. Reset the default parameters
(see Chap. 7.5)
3. If the problem persists, contact
the CARE service center
Shut-
down
Params.
Params.
E2
E130
Hour counter
error
With the machine off check that
there are no defective electrical
connections or faults, then reset the
hour counter (see par. 7.6)
Hour
counter
Reset
manual
Not
active
N/A
E3
E120
Room sensor or
control signal
not connected
Check the connection of the probe,
parameter A2 for the room probe
and the setting of parameter A0
(see page 23)
Shut-
down
Auto
E4
E123
Hi-limit sensor
not connected
Check the connection of the probe,
parameter A6 for the outlet probe
and the setting of parameter A0
(see chap. 7)
Signal
only
Auto
CP
E132
Cylinder being
depleted signal
Perform maintenance and/or
replace the cylinder
Signal
only
Not
active
Auto
CL
E133
Cylinder
depleted signal
cylinder
Perform maintenance and/or
replace the only
Signal
only
Not
Not
active
N/A
EU
E134
machine off
signal
With the machine off:
1. Check for any leaks from the fill
valve or the condensate return pipe
2. Check that the level sensors are
clean total shut-down
Shut-
down
PC
-
Cleaning
cylinder started
signal
You have activated the automatic
cylinder flushing sequence
- - - -
Cy
E135
Timeout signal
(see parameter
"bb") for
maintenance
exceeded
Perform maintenance and/or
replace the cylinder
Signal
only
Manual
reset
hour
counter
Activ
After
the
manual
reset
hour
counter
Nn
E136
Reached final
limit (1.5xbb) of
cylinder
operating life
Replace the cylinder
Shut-
down
Manual
reset
hour
counter
After
the
manual
reset
hour
counter