8
1. General characteristics
1.1 Models available
The various models are differentiated according to the following functions and performance:
operating mode and number of inputs and outputs for versions V, W, Z;
complete versions (hereafter: Top) with serial connection, status LED, fastening from front panel, removable terminals;
compact versions (hereafter: Eco) with fixed terminals and fastening only using rear bracket, and without serial connection;
the power supply can be one of the following: 230 Vac, 115 Vac or 12 Vac/Vdc;
the field of measurement: from -50 to +90 °C (-50 to 127 °F) with resistive NTC probe;
the field of measurement: from -50 to +150 °C (-50 to 127 °F) with resistive PTC probe;
digital input from free contact: in models where featured it is an alternative to the second probe;
relay outputs: available with three different current ratings, 5 A, 8 A and 12 A (for resistive load);
PJ32V
This represents the ideal solution for the management of applications that require simple temperature control of the connected
device (compressor, heaters, valves, etc) .
All V models use one control probe only (S1) and feature a relay with changeover contacts for the control of the actuator.
In some models (PJ32V00, PJ32V0P or PJ32V0H) the second probe can be connected to display the temperature (thermometer
function); this probe has no influence on control.
Models PJ32V0P and PJ32V6P use a relay with changeover contact, 12 A resistive. Model PJ32V0H uses a normally open
relay, 16 A resistive, 2 HP. For all the other models, the normally open relay is 8A resistive.
Both the Top and Eco versions are available, 230 Vac, 115 Vac e 12 Vac/Vdc.
PJ32W
These have been designed for the management of applications where a number of loads need to be controlled or the dual thermostat
function is required.
The W models feature two probe inputs for the temperature control function
Two relay outputs are available for controlling the actuator; the relays used in models PJ32W00 and PJ32W10 are 8 A resistive,
while in models PJ32W0H and PJ32W6H, OUT1 is associated with a 5A changeover relay, and OUT2 uses a normally open
relay, 16 A resistive, 2 HP
PJ32Z
This represents the most complete solution. These models feature three relays, for complete control of up to two actuators and one
alarm output. The 3 relays (8, 5 and 5 A resistive) can be fitted inside a compact container in the versions that feature the 230 Vac
or 115 Vac power supply transformer, without affecting the performance or the reliability of the product.
There are two probe inputs for the temperature control function.
There are three outputs: relay output 1: 8 A resistive, output 2 and alarm output: 5 A resistive.